Application
Indoors or Outdoors in cable ducts, cable trays, conduits or underground locations under mechanical stresses in power and switching stations.
Local distribution systems, Industrial and Commercial units for basic power & lighting purpose.
Conductor Aluminium / Annealed plain copper solid* / stranded conductor conform to IS 7098 / BS 6360 and IEC 60228, Class 2 (Circular / Sector shaped).
Assembly Insulated conductors are laid up together, if necessary interstices may be filled with fillers.
Fillers Non-hygroscopic Poly propylene fillers are included between laid up cores wherever required.
A separator tape of non-hygroscopic poly propylene material is applied over laid up core wherever necessary.
Bedding Bedding Extruded PVC compatible with operating temperature.
Armour For Single Core – Aluminium round wire / flat Strip.
For Multicore – Galvanised Steel round wire / flat Strip.
Outer Sheath Extruded PVC / Special PVC compound such as Flame Retardant (FR), Flame Retardant Low Smoke (FRLS), Low Smoke Zero Halogen (LSOH) can be used for outer sheath to suit a variety of environment and fire risk conditions. Flamabillity test confirms to IEC 332 & Swidish chimeny. For installation where fire and associated problems such as emission of smoke and toxic fumes offer a serious potential threat, special LSF (Low smoke & fumes) compound can be provided. LSF compound is Halogen free (Flourine, Chlorine, Bromine) when tested as per BS 6425 (Pt 1) & IEC 60754 (Pt 1). The acid gas evolved during combustion is less than 0.5% by weight of material.
Insulation PVC type A,C as per IS 5831 / 1984 IEC 60502-1
Single core
Red. Yellow, Blue, Black, Grey or Natural
2 Core
Red, Black
3 Core
Red, Yellow, Blue
4 Core
Red , Yellow, Blue, Black
5 Core
Red, Yellow, Blue, Black & Grey
6 Core & above
Blue , Yellow and remaining core Grey each layer
Minimum Bending Radius 12 times the cable diameter
Admissible Pulling Force Aluminium 30N/Sqmm, copper 50N/Sqmm